Review Status: Completed

Review Details: GRADING

Permit Number - T01BU03302
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2001 LAITH ALSHAMI ENGINEERING REVIEW Denied 1- Provide the Parcel area on the first sheet.
2- Provide basis of bearing which is based on a recorded line between two found survey monuments. Show the basis of bearing on the plan and how it ties into this project.
3- Show the parcel dimensions and bearings.
4- Show and detail all common areas especially for drainage purposes.
5- Show all perimeter and screen walls.
6- Show and detail all curb openings.
7- Show all lot drainage and roof drainage.
8- Contour lines are light. Please darken.
9- Show all proposed finished floor elevations.
10- Show the existing curb along Kolb.
11- Call out erosion hazard setback line and dimension.
12- The detention basin outlet splash pad appears to be smaller than the one shown in the drainage report. Clarify.
13- Demonstrate what happens to the detention basin discharge.
14- Show the project reference # on all sheets.
15- Provide both detention/retention basins dimensions.
16- The spot elevations shown on detail "9" (Basin B) appear to have a discrepancy. Revise.
17- Dimension all sides of the erosion protection. The key-ins should extend beyond the erosion setbacks.
18- The curved arrows on sheet 4 are confusing. Revise.
19- Show the location of the buildings on detail "8" (erosion protection).
20- Tentative Plat must be approved before Grading Plan can be approved.
12/18/2001 LAITH ALSHAMI FLOODPLAIN REVIEW Denied
12/20/2001 LOREN MAKUS NPDES REVIEW Denied
12/21/2001 PATRICIA GILBERT NPPO REVIEW Denied Tentaitve plat approval required. Native plant preservation inspection required to schedule please call, 791-5550 ext. 118.
12/21/2001 PATRICIA GEHLEN ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
12/27/2001 MONICA VALDEZ OUT TO CUSTOMER Completed