Permit Number: T01BU03080
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU03080
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2002 LAITH ALSHAMI FLOODPLAIN REVIEW Denied
03/27/2002 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, 03/27/2002, Drainage and Engineering comments:

1- Fill in the missing information in Grading Note #3
2- Provide the Subdivision Plat number on every sheet.
3- Provide proposed splash pads design.
4- Provide design calculations for the 3-24" RCP's (basin 5)
5- Provide design calculations for the channels west of lots 1-8 & 9-15.
6- Provide design calculations for the channels south of lots 16-22.
7- Details L, K & M on sheet 5 appear to be different from what is addressed in the drainage report.
8- Details D & E were not addressed in the drainage report.
9- The overall development drainage report & Tentative Plat have not been approved. This phase can not be approved until the issues that are raised here and were raised in our last comments have been taken care off.
10- Additional comments may be offered on the next submittal depending on any design changes required to comply with our present and previous comments.
03/28/2002 PATRICIA GILBERT NPPO REVIEW Denied An approved tentative plat is required prior to approval for phase 1.
04/01/2002 LOREN MAKUS NPDES REVIEW Denied
04/01/2002 MICHAEL ST. PAUL ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2002 MONICA VALDEZ OUT TO CUSTOMER Completed