Permit Number: T01BU03080
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU03080
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2001 LAITH ALSHAMI ENGINEERING REVIEW Denied 1- Fill in the missing information in Grading Note #3
2- Provide the Subdivision Plat number on every sheet.
3- Provide proposed splash pads design.
4- Provide design calculations for the 3-24" RCP's (basin 5)
5- Provide design calculations for the channels west of lots 1-8 & 9-15.
6- Provide design calculations for the channels south of lots 16-22.
7- Details L, K & M on sheet 5 appear to be different from what is addressed in the drainage report.
8- Details D & E were not addressed in the drainage report.
9- The overall development drainage report & Tentative Plat have not been approved. This phase can not be approved until the issues that are raised here and were raised in our last comments have been taken care off.
10- Additional comments may be offered on the next submittal depending on any design changes required to comply with our present and previous comments.
11/20/2001 LAITH ALSHAMI FLOODPLAIN REVIEW Denied
11/26/2001 PATRICIA GILBERT NPPO REVIEW Denied
11/26/2001 PATRICIA GEHLEN ZONING REVIEW Denied
11/28/2001 LOREN MAKUS NPDES REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2002 CINDY AGUILAR OUT TO CUSTOMER Completed