Permit Number - T01BU02708
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2001 | ESTEVAN TINEO | ENGINEERING | REVIEW | Denied | 1. The proposed grading is not in accordance to the 2000 IBC, Chapter 36 (admendment) grading Ordinace; the north-end of the proposed building pad elevations exceeds 2-feet of fill over the existing grades. Please see Chapter 36, Section 13. 2. The plan proposes large fills but does not indicate fill slopes and or retaining walls. Provide this information per chapter 36 of the grading Ordinace. Revise. 3. Structural retaining walls should be designed by a registered Structural Engineer and submitted to COT Structural review. |
| 09/20/2001 | ESTEVAN TINEO | FLOODPLAIN | REVIEW | Denied | See comments in Floodplain. |
| 09/21/2001 | JOE LINVILLE | NPPO | REVIEW | Denied | Per the Tentative Plat/Development Plan Lot 2 requires vegetation replacement as follows: 8 15 gal. "foothill Palo verde" trees. Upland seed mix for disturbed portions of the site. Indicate compliance with these requirements on the plan. See the attached Hillside Development Site Improvement Standard and include additional site information in compliance with the standard. Add as general notes the highlighted portions of the attached standard. |
| 09/21/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | |
| 09/24/2001 | CAGUILAR | NPDES | REVIEW | Passed |