Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T01BU02579
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2001 | ESTEVAN TINEO | FLOODPLAIN | REVIEW | Denied | See comments in the END Folder. |
| 09/06/2001 | ESTEVAN TINEO | ENGINEERING | REVIEW | Denied | The Plans must be prepared per Chapter 36 of the Grading Ordinace; Since large fills are proposed for this project, this should be designed per "Engineered Grading Requirements", see section 9.4 for submittal requirements. In addtion, the plans should detail the proposed retaining walls, and include structural calculations. The Plan should include the erosion hazard setback and floodplain limits on the Plan. |
| 09/07/2001 | PATRICIA GILBERT | NPPO | REVIEW | Denied | An approved site and native plant preservation is required. |
| 09/10/2001 | SREEVES | NPDES | REVIEW | Passed | |
| 09/10/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/21/2001 | JKOZUCH | OUT TO CUSTOMER | Completed |