Permit Number: T01BU02508
Parcel: 141130110

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU02508
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2001 DOUG WILLIAMS NPDES REVIEW Passed
12/03/2001 DOUG WILLIAMS ENGINEERING REVIEW Denied . Project addresses vary on C-2.2
. Cut/Fill qty's vary on above sheet and grading permit application - revise as necessary.
. Depict the limits of grading.
. Include a copy of the Development Plan with next submittal...must have a copy of the approved Development Plan with submittal prior to approval/issuance of grading permit.
. Provide written notification/permission (notarized) of offsite grading.
. Reference COT/PC SD 209 for curb and gutter construction - see redlines on details sheet (re. dimensions and radii)
. See redline comments on plans.
12/03/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied
12/04/2001 PATRICIA GILBERT NPPO REVIEW Denied An approved Development Plan is required. Pre-permit inspection is required. To schedule please call 791-5550, ex. 118.
12/04/2001 MICHAEL ST. PAUL ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
12/05/2001 LISA LESNY OUT TO CUSTOMER Completed