Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2001 LAITH ALSHAMI ENGINEERING REVIEW Denied 1- The building closest to Tanque Verde does not meet the requirements of the differential grading Ordinance.
2- The water depth in detail 6/c.2.3 does not match the previously approved grading plan. Clarify.
3- The large detention/retention basin, in the middle of the proposed development is smaller than what was approved previously.

Submit a revised drainage report to address the several drainage modifications.