Permit Number: T01BU02371
Parcel: 117071910

Address:
124 W 18TH ST

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU02371
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2001 TOM WEIDEMAN ENGINEERING REVIEW Denied DATE: August 27, 2001

FROM: Engineering Section


SUBJECT Barrio Viejo Elderly Housing Site Plan
T01BU02317

COMMENTS: The Grading Plan has been reviewed and is not acceptable. Please address the
following comments.


1. Provide details of all the catch basins and grates being used, specifically construction keynotes # 23b, 24a, 24b and 25.
2. It appears keynote #3 being shown along the north boundary referencing the 12" pipe should read keynote #33.
3. Should the second catch basin south of South Rubio, invert 92.35, be referencing keynote 24a instead of 24b?
4. Call out if South Rubio will be closed off at the north property line.
5. It appears keynote #13 shown just south of the retention catch basin is incorrectly referencing rip-rap at a sidewalk scupper.
6. All the harvesting areas as shown on the site plan should not have drainage piping attached as this defeats the purpose of water harvesting. Make the appropriate corrections to the harvesting areas per site plan comment #9. Correct construction keynote #28 accordingly.
7. Indicate piping to the catch basin or "other areas as shown on the plans" in typical detail #9, the roof downspout.
8. Back of sidewalk curbing should be shown in typical detail #6, access ramp as appropriate to each ramp.
9. Item #1 under the grading notes should call out the International Building Codes (IBC), Chapter 36.
10. Provide an administrative address for the site.
11. Provide appropriate sheet numbers.


Items Required: Revised Grading Plan
Re-submittal Required: Yes


If you have any questions on the above comments feel free to call Tom Weideman at 791-4942. My E-mail address is tweidema@ci.tucson.az.us.
08/27/2001 DAVID RIVERA ZONING REVIEW Denied
08/27/2001 TOM WEIDEMAN FLOODPLAIN REVIEW Denied DATE: August 27, 2001

FROM: Engineering Section


SUBJECT Barrio Viejo Elderly Housing Site Plan
T01BU02317

COMMENTS: The Grading Plan has been reviewed and is not acceptable. Please address the
following comments.


1. Provide details of all the catch basins and grates being used, specifically construction keynotes # 23b, 24a, 24b and 25.
2. It appears keynote #3 being shown along the north boundary referencing the 12" pipe should read keynote #33.
3. Should the second catch basin south of South Rubio, invert 92.35, be referencing keynote 24a instead of 24b?
4. Call out if South Rubio will be closed off at the north property line.
5. It appears keynote #13 shown just south of the retention catch basin is incorrectly referencing rip-rap at a sidewalk scupper.
6. All the harvesting areas as shown on the site plan should not have drainage piping attached as this defeats the purpose of water harvesting. Make the appropriate corrections to the harvesting areas per site plan comment #9. Correct construction keynote #28 accordingly.
7. Indicate piping to the catch basin or "other areas as shown on the plans" in typical detail #9, the roof downspout.
8. Back of sidewalk curbing should be shown in typical detail #6, access ramp as appropriate to each ramp.
9. Item #1 under the grading notes should call out the International Building Codes (IBC), Chapter 36.
10. Provide an administrative address for the site.
11. Provide appropriate sheet numbers.


Items Required: Revised Grading Plan
Re-submittal Required: Yes


If you have any questions on the above comments feel free to call Tom Weideman at 791-4942. My E-mail address is tweidema@ci.tucson.az.us.
09/11/2001 PATRICIA GILBERT NPPO REVIEW Denied An approved site plan is required. Pre-permit inspection is required to schedule please call, 791-5550 ext. 118.
09/25/2001 CAGUILAR NPDES REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2001 TAMI ACHONG OUT TO CUSTOMER Completed