Permit Number: T01BU02260
Parcel: Unknown

Address:
198 S GRANADA AV

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU02260
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2002 MATT FLICK ENGINEERING REVIEW Denied Engineering: Comments #1, #4, #5, #6, and #7 from the 7SEP01 engineering review have not been addressed.

Regarding the drainage statement submitted with these plans: The consultant must certify as to the accuracy and reasonableness of the revised discharge used in the analysis prior to using it in the design calculations. The discharge used from another report was not approved for design purposes, only platting purposes.

Provide approved site plan with future submittals.
08/23/2002 MATT FLICK FLOODPLAIN REVIEW Denied FLOODPLAIN: The previous floodplain use permit application (T02OT00353) was denied. A floodplain use permit is required for this project and depends upon several conditions listed in the comments listed in T02OT00353.
08/26/2002 MSTPAUL1 NPDES REVIEW Passed
08/26/2002 MICHAEL ST. PAUL ZONING REVIEW Denied Floodplain and Engineering approval required.
08/26/2002 PATRICIA GILBERT NPPO REVIEW Passed passed on 8/01

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2002 LISA LESNY OUT TO CUSTOMER Completed