Permit Number: T01BU02260
Parcel: Unknown

Address:
198 S GRANADA AV

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU02260
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2001 TOM WEIDEMAN ENGINEERING REVIEW Denied 1. A floodplain use permit is required prior to approval of this plan. Please provide the permit with the re-submittal.
2. Provide cross-sections / details of where the new earthen drainage channel ties into the existing concrete channel located at the southwesterly corner of the development.
3. On sheet 2 the trash enclosure location should call out detail A/2, not A/3.
4. Keynote #7 on sheet 2 should state "the enclosure will be constructed per development standard 6-01, at a minimum".
5. Modify the enclosure detail A/2 to show bollards on three sides of the structure per the standards.
6. Keynote #19 on sheet 3 should call out sheet 4, not 5.
7. It appears typical sections A/4, B/4, C/4, D/4, E/4 and H/4 are not called out in the keynotes on sheets 2 and 3. Please reference these typicals in the appropriate keynotes on sheets 2 and 3.
09/07/2001 TOM WEIDEMAN FLOODPLAIN REVIEW Denied
09/10/2001 PATRICIA GEHLEN ZONING REVIEW Denied
09/10/2001 LOREN MAKUS NPDES REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2001 TAMI ACHONG OUT TO CUSTOMER Completed