Permit Number: T01BU02212
Parcel: 11446022C

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU02212
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2001 TOM WEIDEMAN ENGINEERING REVIEW Denied DATE: August 13, 2001

FROM: Engineering Section

SUBJECT La Villa at Vista Del Rio
T01BU02212

COMMENTS: The Grading Plan has been reviewed and is not acceptable. Please address the following
comments on the plan for review and approval.

1. Provide a general note stating the development shall meet the engineered grading requirements per chapter 36 of the 2000 IBC because cut / fill is greater than 5000 cu. yds.
2. Locate detail E / 1 on the plans.
3. Provide a two-foot horizontal barrier around the basin top edge per chapter 14 of the 2000 IBC.
4. Call out the size of the drain holes located along the south property line.
5. Per the approved plat show the 100-yr floodplain limits along Dos Hombres and Desert Arbors. Include the associated 100-yr. water surface elevations.
6. Curbing, sidewalk and an appropriate sized scupper is required on the south side of Desert Arbors at the northwesterly property corner extending from the existing curbing moving west to the end of the property. Please provide appropriate details and make the appropriate corrections to the plans.
7. Call out the required curbing, sidewalk and scupper in detail J /2.
8. Submit a copy of the approved tentative plat ( showing the proper stamps ) with the re-submittal.



Items Required: Revised Grading Plan
Re-submittal Required: Yes


If you have any questions on the above comments feel free to call Tom Weideman at 791-4942.
08/13/2001 PATRICIA GILBERT NPPO REVIEW Denied Native Plant Pre-permit inspection is required, call to schedule 791-5550 ext. 118.
08/13/2001 TOM WEIDEMAN FLOODPLAIN REVIEW Denied
08/13/2001 PATRICIA GEHLEN ZONING REVIEW Denied
08/14/2001 SREEVES NPDES REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2001 SUE REEVES OUT TO CUSTOMER Completed