Permit Number: T01BU02074
Parcel: 138241680

Review Status: Stopped

Review Details: GRADING

Permit Number - T01BU02074
Review Name: GRADING
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2001 STEVE TINEO ENGINEERING REVIEW Denied Per the grading ordinace, fill of excess of 5000 cubic yards are classified as Engineered Grading and require submittal per section 9.4, 9.5, and 9.6 of Chapter 36, amendment to the 2000 IBC, please revise. In addition, the approved development plan must be included in the package.
07/23/2001 ESTEVAN TINEO FLOODPLAIN REVIEW Denied The approved development plan or a copy of the development plan should be included for reference. The approved development plan must be included for approval of the grading plan.
07/24/2001 LOREN MAKUS NPDES REVIEW Denied
07/24/2001 PATRICIA GILBERT NPPO REVIEW Denied PRE-INSPECTION IS REQUIRED. CALL TO SCHEDULE; 791-5550 EXT. 118.
07/24/2001 PATRICIA GEHLEN ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2001 ELAINE ROSE OUT TO CUSTOMER Stop
07/24/2001 JKOZUCH REJECT SHELF Completed