Permit Number: T01BU01972
Parcel: Unknown

Address:
1951 N WILMOT RD

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU01972
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2004 Laith Alshami ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/24/2004

The submittal, which was necessitated by field modifications to what was previously approved, and the Engineering Field Inspector Punch List Comments, can not be reviewed as submitted. It appears that the submittal does not address all the punch list items. In order to facilitate the review of the as-built plans, provide a detailed response letter to the punch list items, explaining how the new modifications meet the City requirements.

Please be advised that roof drainage should be put through scuppers anywhere it crosses sidewalks/walkways, no matter how small the runoff is.

You may contact me at 791-5550, Ext. 1195 or at my email address: Laith.Alshami@tucsonaz.gov
03/24/2004 DAVID RIVERA ZONING REVIEW Denied Zoning will review and approve the grading plan upon approval by the Engineering Section.
03/25/2004 Andrew Connor NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed
03/25/2004 SUE REEVES REJECT SHELF Completed