Permit Number: T01BU01918
Parcel: 13319195A

Review Status: Completed

Review Details: GRADING

Permit Number - T01BU01918
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2002 LAITH ALSHAMI ENGINEERING REVIEW Denied Comments by Laith Alshami, 1/15/2002:

1- Show spot elevations or cross-sections for the proposed detention and retention basins to provide adequate construction details and verify that security barriers are not required.
2- provide maintenance ramps for the detention and retention basins.
3- has the propsed one way egress been approved by Mayor and Council.
4- An approved Development Plan is required before the Grading Plan can be approved.
01/15/2002 PATRICIA GILBERT NPPO REVIEW Denied
01/15/2002 LAITH ALSHAMI FLOODPLAIN REVIEW Denied
01/15/2002 PATRICIA GEHLEN ZONING REVIEW Denied
01/16/2002 MVALDEZ NPDES REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2002 LISA LESNY OUT TO CUSTOMER Completed