Review Details: PLUMBING
Permit Number - T00PL01752
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide the waste fixture units on the plan. 2. Provide the water fixture units on the plan. NOTE: Both of the above CAN NOT be the same. 3. Provide the slope of ALL sewer lines on the plan. 4. Provide readable water demand calculations and put them on the plans. TAKE NOTE : If the waste fixture units go over 720-- a 8" sewer will be required. |
| 02/02/2001 | TGRIFFUS | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 02/02/2001 | DELMA ROBEY | REJECT SHELF | Completed |