Review Status: Completed
Review Details: PLUMBING
Permit Number - T00PL01752
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide the basis of elevation on the plan. 2. provide the waste fixture units for each building on the plan.3. Provide the slope of all sewer lines on the plan.4. Provide the profile of the sewer going under any drainage way ie: 16 detail 5 on sheet 6 & sewer line South West of this note. Note: The 8" sewer shall comply with Sec 713.1.1UPC1994 as amended- Man Holes are required. Note: If the Water piping is to be approved with this plan please provide the following; What type of fixtures for each building & the amount. A water demand calculation for each group of buildings based on APPENDIX A UPC1994 will be required. |
| 09/22/2000 | RAY MORGAN | WWM | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/01/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |