Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T00PL01752
Parcel: 13311004C

Review Status: Completed

Review Details: PLUMBING

Permit Number - T00PL01752
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide the basis of elevation on the plan. 2. provide the waste fixture units for each building on the plan.3. Provide the slope of all sewer lines on the plan.4. Provide the profile of the sewer going under any drainage way ie: 16 detail 5 on sheet 6 & sewer line South West of this note. Note: The 8" sewer shall comply with Sec 713.1.1UPC1994 as amended- Man Holes are required. Note: If the Water piping is to be approved with this plan please provide the following; What type of fixtures for each building & the amount. A water demand calculation for each group of buildings based on APPENDIX A UPC1994 will be required.
09/22/2000 RAY MORGAN WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2001 DELMA ROBEY OUT TO CUSTOMER Completed