Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T00MH00430
Parcel: 11810134B

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD

Permit Number - T00MH00430
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2000 DAVE WILLETT BUILDING-RESIDENTIAL REVIEW Approved
08/16/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Approved hold final per fpup #398
08/16/2000 DAN CASTRO ZONING REVIEW Approved