Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T00EL02001
Parcel: 129120240

Address:
1020 E 26TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T00EL02001
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2000 TERRY STEVENS ELECTRICAL-COMMERCIAL REVIEW Approved