Review Details: SITE
Permit Number - T00CM06118
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2001 | JIM EGAN | FIRE | REVIEW | Denied | |
| 06/04/2001 | PHIL SEADER | HANDICAP-SITE | REVIEW | Approved | |
| 06/12/2001 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | |
| 06/12/2001 | DOUG WILLIAMS | SANITATION | REVIEW | Approved | |
| 06/12/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 06/18/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | |
| 07/02/2001 | JOE LINVILLE | NPPO | REVIEW | Approved | Class 1 exc. |
| 07/02/2001 | JOE LINVILLE | LANDSCAPE | REVIEW | Denied | 1. Canopy trees within the vehicle use area must be evenly distributed per LUC 3.7.2.3.A.1.a. STOP. 2. The screen walls proposed along Camino Seco and Speedway extend in to the street landscape borders more than the 3' maximum allowed in LUC 3.7.3.2.C.3. STOP.. 3. The loading zone must be screened from Camino Seco with a 6' masonry wall. LUC 3.7.3. STOP. 3. Parking spaces may not extend or overhang into the street landscape borders per DS 2-06.3.3.E. Revise plan to comply. END. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/24/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |