Permit Number: T00CM05804
Parcel: 133160470

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T00CM05804
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2000 JIM EGAN FIRE REVIEW Approved
12/04/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
12/04/2000 DAVID RIVERA ZONING REVIEW Approved
12/04/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
12/04/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
12/07/2000 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied SH X1 CODE REVIEW CHECK LIST
REVISE PER TELECON 12/7 OCCUPANT LOAD (SHOWROOM /100)
EXITS THREE (EAST & WEST ENDS & MIDDLE)
SH A1 DET. 11 DIMENSION 2' 5" @ APRON TO FLOOR.
SH A2 eNLARGED RESTROOM PLAN - PROVIDE 2'-6'
CLEAR DIMENSION @ URINAL.
SH A3 DOOR & HARDWARE SCHEDULE
DOORS 013A & 013B SHALL HAVE NON-LOCKING FUNCTION
DOOR 013D PROVIDE PANIC EXITING DEVICE.
DETAIL 7 UNNECESSARY.
DETAIL 8 DIMENSION MIN. SILL HEIGHT.
12/11/2000 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
12/14/2000 CBUFORD WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/14/2000 CLAUDIA BUFORD APPROVAL SHELF Passed
12/14/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
12/14/2000 CLAUDIA BUFORD REJECT SHELF Passed