Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T00CM05667
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/01/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/09/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SEE PRIOR COMMENT # 1. THE 'NEW' FLOOR PROVIDED FOR EQUIPMENT SUPPORT ON STRUCTURAL DRAWING S-1 TO BE ADDRESSED ARCHITECTURALLY AS TO BUILDING CODE REQUIREMENTS ie: WHERE IS THIS FLOOR LOCATED HEIGHTWISE IN THE BUILDING? WHAT ARE THE FIRE-RATING REQUIREMENTS ? HOW IS THE FLOOR TO BE FINISHED? etc. 2. SEE PRIOR COMMENT #2. CLARIFY ACCESSIBILITY, SHOW BY ESTIMATE AND ON DRAWINGS, WHERE 20% OF PROJECT VALUATION IS SPENT ON ACCESSIBILITY. 3. SEE PRIOR COMMENT #6. SHOW HOW FIRE-RATINGS ARE PROVIDED AND MAINTAINED .PROVIDE A COPY OF THE FIRE ASSEMBLY LISTINGS ON THE DRAWINGS , AS WELL AS THE CONSTRUCTION DETAILS TO COMPLY WITH THE LISTINGS, AT SHAFTS, NEW FLOOR FRAMING, OVER HOOD/S, AT REINFORCING OF FLOOR CEILING ASSEMBLY OVER KITCHEN AREA ,ETC. |
| 02/09/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 4. LETTER OF AGREEMENT ON HOW PREVIOUSLY UNPERMITTED PORTIONS OF THE WORK WILL BE HANDLED APPROVED BY BUILDING OWNER AND DEVELOPMENT SERVICES. |
| 02/12/2001 | TGRIFFUS | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/12/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |