Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T00CM05667
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2001 | DLAAKSO | BUILDING-RESIDENTIAL | REVIEW | Denied | 1) CHANGE OF OCCUPANCY REQUIRES AREA OF CHANGE TO MEET CURRENT CODE ( 1994 UBC AS AMENDED). ............ ........1. PRESERVATIVE PRESSURE -TREATED BOTTOM PLATE REQUIRED AT WOOD FRAME WALLS PER UBC SEC #2317.4. ............................................................................................. .......2. PROVIDE DETAILS FOR "NEW" DOOR OPENINGS AT OFFICES #1,#2, AND #3 ADDRESS:.............................................. ..............1. STRUCTURAL REQUIREMENTS................................. ..............2. ARCHITECTURAL REQUIREMENTS, INCLUDING LANDINGS, HARDWARE, RAMPS, etc., PER UBC SEC #1004, #1007, #1106. ..................................................................................... .......3. PROVIDE DETAILS FOR EXISTING DOORS TO SHOW CONFORMANCE WITH CURRENT CODE , ie: HARDWARE, LANDINGS, RAMPS PER UBC SEC #1004, #1007, #1106. ........... .......4. CLARIFY FIRE RATING OF DOOR ASSEMBLY TO SERVER AREA TO MAINTAIN ONE-HOUR FIRE-RATED CORRIDOR. ....................................................................................... .......5.VERIFY AND PROVIDE OPENING PROTECTION AT ONE-HOUR FIRE-RATED CORRIDOR. .......................................... .......6. CLARIFY 12" EXTENSIONS ,LEVEL WITH FLOOR AT EACH RAMP ,TOP AND BOTTOM. |
| 04/20/2001 | JIM EGAN | FIRE | REVIEW | Denied | 1. INDCIATE DOORS PROVIDED WITH PANIC HARDWARE. IF THE THREE DOORS IN THE SOUTH EXTERIOR WALL ARE TO REMAIN, THEY MUST BE PROVIDED WITH EXIT HARDWARE REQUIRED FOR EXIT DOORS FOR ASSEMBLY OCCCUPANCIES. |
| 04/20/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 04/24/2001 | DROBEY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 04/24/2001 | DROBEY | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/24/2001 | DROBEY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/24/2001 | FRANK KALINSKI | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/26/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |