Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T00CM05633
Parcel: Unknown

Address:
7250 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T00CM05633
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
ELECTRICAL REVIEW COMMENTS

1) Provide the nameplate current on the mechanical equipment.
2) Provide data on the UPS system. Is there a main and separate overcurrent devices on the UPS?
3) Provide a complete single line diagram of the electrical service.
4) Show location, service capacity, calculated loads, conduit and wire sizes, fault current analysis, ect.
5) Provide complete panel schedule showing the circuit numbers, loads in VA, phasing and description.
6) Provide a load calculation showing the loads on all phases. (Balance all loads within 15% of each other. Add 25% for continuous loads.
7) Provide fixture wattages and total watts including ballast losses.
8) The transformers shall be grounded per 99NEC 250-30(3)(a)(b).
9) Provide information on capabilities of the buck-boost transformer.All the data I have show that they have a limit + or - 20%.
10) Provide sizing of grounding electrode conductor (at transformer)
11) Provide size of flex.metalic conduit
11/21/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/21/2000 JIM EGAN FIRE REVIEW Approved
11/21/2000 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
11/21/2000 PETER MCLAUGHLIN ZONING REVIEW Passed
11/22/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Passed
11/22/2000 RAY MORGAN WWM REVIEW Passed
11/22/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Provide all of the equipment data on the plan. 2.The dry well is to be 60 inch. deep. 3. PVC can not be used in this type building.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2001 TAMI ACHONG APPROVAL SHELF Completed
12/04/2000 TAMI ACHONG OUT TO CUSTOMER Completed
11/24/2000 TAMI ACHONG REJECT SHELF Completed
11/24/2000 TAMI ACHONG REJECT SHELF Completed