Permit Number: T00CM05551
Parcel: 122172750

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T00CM05551
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2001 JIM EGAN FIRE REVIEW Approved
06/13/2001 INGA DAVIDSON WATER REVIEW Approv-Cond
06/13/2001 PATRICIA GEHLEN ZONING REVIEW Denied
06/13/2001 GERRY KOZIOL WWM REVIEW Approved
06/14/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Show on the plan how the mechanical design complies with Chapter 4 and 5 IMC 2000. 2. Access to equipment on the roof shall comply with Sec306.5 IMC 2000. 3. Condensate shall comply with Sec307 IMC 2000..
06/14/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide a clean out at the bar sink. 2. Comply with Sec 511.2 UPC 1994 Az. Code for the water heater. 3. Provide a water demand calculation based on Appendix A UPC 1994 Az. Code.
06/15/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
06/26/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/26/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
07/03/2001 JKOZUCH OUT TO CUSTOMER Completed