Permit Number: T00CM05515
Parcel: 107030650

Address:
1925 W SPRING ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T00CM05515
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/14/2000 DRIVERA NPPO REVIEW Passed
11/14/2000 DAVID RIVERA ZONING REVIEW Approved
12/04/2000 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T00CM05515
12/5/00

PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND.

GENERAL REQUIREMENTS

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLAN

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS, OR STATE THAT THE ASSUMED VALUE OF 1,000 PSF IS BEING USED.

FLOOR PLAN

1. SHOW COMPLIANCE WITH UBC SEC 1203.2 PROVIDING NATURAL LIGHT INTO ROOMS.
MISSING FOR BEDROOM #1-----ADJACENT WALL MUST BE MORE THAN 50% OPEN

2. SHOW COMPLIANCE WITH UBC SEC 1203.3 PROVIDING NATURAL VENTILATION.
MISSING FOR BEDROOM #1-----ADJACENT WALL MUST BE MORE THAN 50% OPEN

3. SHOW COMPLIANCE WITH UBC SEC 310.4 PROVIDING EGRESS FROM BEDROOMS OR BASEMENTS. SHOW MAXIMUM SILL HEIGHT OF 44".
MISSING FOR BEDROOM #1-----ADJACENT WALL MUST BE MORE THAN 50% OPEN TO USE WINDOW OF DRESSING ROOM FOR EGRESS
WINDOWS IN BEDROOMS #4 & #5 DO NOT MEET MIN. REQUIREMENTS----
HORIZONTAL OPENING MIN. 20"

4. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE. DESIGNATE LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22"X30" THE LOCATION OF THE ATTIC ACCESS SHALL PROVIDE A MINIMUM OF 30" OF HEADROOM. UBC SEC 1505.1----------SEE MECH. PLAN

5. MIN. WIDTH OF A HABITUAL ROOM IS 7'------BEDROOM #4 DOES NOT MEET THIS CODE REQUIREMENT.

ELEVATIONS

1. NOTE AND SPECIFY ALL ROOF SLOPES. MINIMUM ROOF SLOPE 3/8" PER FOOT. UBC SEC 1506.1 AND LOCAL AMENDMENT.
NOTE: PORCH ROOF SLOPE APPEARS TO BE FLAT

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS: @ 791-5550 EXT. 112
12/06/2000 RAY MORGAN WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2000 CLAUDIA BUFORD APPROVAL SHELF Passed
12/11/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
12/07/2000 CLAUDIA BUFORD REJECT SHELF Passed