Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2001 DAN CASTRO ZONING REVIEW Approved
03/22/2001 DCASTRO NPPO REVIEW Passed
03/27/2001 GERRY KOZIOL WWM REVIEW Approved
03/27/2001 JIM JOHNSEN FLOODPLAIN REVIEW Approved
04/05/2001 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T00CM05499
4/5/01

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating the action taken.

GENERAL REQUIREMENTS:

1. All corrections and revisions shall be made on the original tracings. Return all redlined prints. The final package shall consist of two sets of drawings and related documents, one which the City shall retain and the other set will be stamped and returned to you.

SITE PLAN:

1. Provide dimensions from all structures to property lines, and show distances between all structures.

Note: Min. distance between two single family residences is 6' [assumed property lines] with out a one hour rated firewall. It appears a firewall is required between existing porch and new house and between existing and new carports.

FOUNDATION PLAN:

1. Footing widths for one-story, per Table R403.1:
- 19" minimum; hollow concrete/masonry

STRUCTURAL PLANS:

1. Center 6x10 HF SS at carport appears to be inadequate-------change or submit calcs.

2. Include complete details of required firewalls.

ELEVATIONS:

1. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.

SECTIONS - DETAILS - MISC. NOTES:

1. Note and specify the size, spacing and length of embedment of anchor bolts for sill plates, top plates and ledgers.

PLUMBING PLANS:

1. Provide pressure and temperature relief valve at water heater, per P2803.

2. Waste line as indicated in or under footing is not allowed as per UPC.

3. Waste vent missing for tub/shower.

MODEL ENERGY CODE:

1. Provide Energy Calculations per IECC, or comply with IRC Chapter 11.

2. Call out on the plans the "R" values of insulation, as well as the "U" values of the windows and doors in conformance with the energy calculations provided.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS: @ 791-5550 EXT. 112

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2001 MONICA VALDEZ OUT TO CUSTOMER Completed