Permit Number: T00CM05496
Parcel: 14016006A

Address:
5102 S CHERRY AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T00CM05496
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2000 PATRICIA GEHLEN ZONING REVIEW Passed
11/21/2000 JIM EGAN FIRE REVIEW Approved
12/18/2000 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied SH A4.4 DET. 3 WALL SECTION @ C.R.106
FIRESTOP FURR OUT @ TERMINATION OF GYP. BD.
DET. 4 DETAIL FRAMING AT SKLYLIGHT. SPACING AND
CONNECTIONS. DETAIL SUSPENSION OF GYP. BD. CLG.
SH A4.3 NOT SUBMITTED. LOOKING FOR DET. 2 & 3 SH.
A4.3.
SH. 6.2 DETAIL TRANSITION DOWN TO 7' 2" GWB FROM
ACT ACT 8'6" MAINTAIN 1 HR RATED CEILING CONST.
SH. A8.0 PROVIDE OVERFLOW SCUPPER THROUGH PARAPET ADJACENT TO DOWNSPOUTS OR DROP TOP
OF LEADERBOX TO INVERT OF SCUPPER THROUGH
PARAPET.
DET. 20 WHERE DOES IT OCCUR?
DETAIL 16 PROVIDE ONE HOUR RATED TRANSITION
BETWEEN GYP. BD. CLG. OF ACOUSTICAL PANELS.
12/19/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-3.1
1)Circuit H5 appears overloaded. 45 D fixtures X 105 VA/fix = 4725vA. 4725VA / 277V = 17A. 17A (X) 125% = 21.3A
2) There is not a G type fixture in the schedule however there are 15 G fixtures on the plan.
E3.2
1) The loads serving circuits L-2, 12,11,9, and 7 appear incorrect.
2) It does not appear panel schedule L matches the plan (i.e.) L-1, 3, 5, and 11.
3) A receptacle serving a TV in room 103 lacks a circuit number.
4) Describe the Air Conditioner disconnects and fuse requirements.
E3.4
1) The ground from the transformer secondary to panel L must be a number 4 copper minimum. 99NEC 250-102(c).
2) The neutral serving the panel CPC must be a minimum of 1/0. 99NEC 310-4
3) Provide panel CPB ampacity.
GENERAL COMMENT
1) Provide an MEC lighting budget analysis.
12/20/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide a complete waste line isometric drawing. 2. Provide the total length of 3/4" MPG line on the plan. Note: P1.2 indicates this line as 1/2"--- which is it? 3. Provide a manual shut off valve ahead of the pressure regulator per Sec1218.5UPC1994. 4. Provide the total length of gas line down stream of the pressure regulator on the plan. 5. Provide the manufactures name and listing for all of the plumbing fixtures on the plan.
12/20/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Architectural detail 3 on A4.4 does not meet the Model Energy Code. 2. How come there are TWO detail 14's on sheet A-8.0. Note: Call outs on sheet A-7.2. Indicate on sheet A-8.0 an Over Flow Roof Drain detail. Note: If the parapet between the old building and the new building is 30" or higher, a cross over ladder will be required-- Sec 321.8 #3 UMC1994. 3. All penetrations into the rated corridor will require a Fire/Smoke damper. Provide and show on the plan.
12/22/2000 RAY MORGAN WWM REVIEW Approved
12/22/2000 CBUFORD WATER REVIEW Approved
12/27/2000 CBUFORD FLOODPLAIN REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2001 DELMA ROBEY OUT TO CUSTOMER Completed
01/12/2001 DELMA ROBEY REJECT SHELF Completed
01/12/2001 DELMA ROBEY APPROVAL SHELF Completed