Permit Number: T00CM05492
Parcel: 12907006R

Address:
2420 S KINO PW

Review Status: Completed

Review Details: SITE

Permit Number - T00CM05492
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2001 EROSE SANITATION REVIEW Needs Review
01/19/2001 EROSE ENGINEERING REVIEW Needs Review
01/19/2001 EROSE HANDICAP-SITE REVIEW Needs Review
11/13/2000 JIM EGAN FIRE REVIEW Denied 1. SUBMIT SITE TO TO SCALE.
2. FIRE ACCESS ROADWAY MUST BE PROVIDED AND EXTENDED TO WITHIN 150 OF ALL PORTIONS OF EXTERIOR WALLS OF STRUCTURE. ROADWAY SHALL BE MINIMUM 20 FEET WIDE, PAVED. tURNAROUND REQUIRED FOR DEAD-END ROADWAY.
3. FIRE HYDRANT REQUIRED.
11/20/2000 JJOHNSEN FLOODPLAIN REVIEW Denied Unable to perform complete review. Site plan sheet A0.1 only states that site work will be by separate contract and does not include most of the information required by Development Standard 2-02, such as drainage patterns, proposed finished floor elevations, finish grades, topographic information. There is a note in the lower right corner of this sheet which states to refer to the approved site plan. If this note refers to T99CM03220, that site plan did not include the site work for this building, and infact stated it was to be accomplished by others.
12/06/2000 DAVID RIVERA ZONING REVIEW Denied
12/07/2000 JOE LINVILLE NPPO REVIEW Denied submit any previous approvals related to native plant preservation
12/07/2000 JOE LINVILLE LANDSCAPE REVIEW Denied Submit previously approved site and landscape plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2001 ELAINE ROSE OUT TO CUSTOMER Completed