Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T00CM05492
Parcel: 12907006R

Address:
2420 S KINO PW

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T00CM05492
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2001 EROSE WATER REVIEW Passed
01/19/2001 EROSE WWM REVIEW Passed
11/13/2000 JIM EGAN FIRE REVIEW Denied 1. SUBMIT SITE PLAN TO SCALE.
2. MINIMUM 20 FEET WIDE PAVED FIRE APPARATUS ACCESS ROADWAY MUST BE PROVIDED AND EXTENDED TO WITHIN 150 FEET OF ALL PORTIONS OF EXTERIOR WALLS OF STRUCTURE. TURNAROUND REQUIRED FOR DEAD-END ROADWAYS.
3. FIRE HYDRANT REQUIRED.
11/13/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied GENERAL COMMENTS
1) Provide a fixture cut and catalog number for fixture "B". (C.O.T. Ordinance. 8210)
2) Provide M.E.C. calculations. (C.O.T. ordinance 8351)
3) Provide an electrical site plan depicting the utility transformer and the service location.
E1.1
1) Provide #10 wire for circuit 8, in addition hardwire the connection and provide a disconnect. (99NEC 422-31(b), 310-16, and 240-3(d))
2) Circuit S2 is used twice. It is serving both the exterior lights and the refrigerator.
3) Two receptacles in the electrical corridor lack circuit number.
E2.1
1) The available fault is called out as 13,900 amps however the meter is rated 10,000 amps.
2) Remove the ground wire from the service lateral. It effectively parallels the neutral and the ground. Thus current would flow on the ground wire during normal operation.
11/20/2000 JJOHNSEN FLOODPLAIN REVIEW Denied Unable to perform complete review. Site plan sheet A0.1 only states that site work will be by separate contract and does not include most of the information required by Development Standard 2-02, such as drainage patterns, proposed finished floor elevations, finish grades, topographic information. There is a note in the lower right corner of this sheet which states to refer to the approved site plan. If this note refers to T99CM03220, that site plan did not include the site work for this building, and infact stated it was to be accomplished by others.
11/22/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
11/22/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Plumbing 1. Provide a civil site plan with the up & down stream M.H. or C.O. Rim elev., Inverts of same, F.F.E. of the building-Water & Sewer lines and size of same. 2. What size is the waste line from the P-7? 3. Provide the manufactures name & listing for the P-7 & P-8. 4. Provide an expansion tank for the water heater, show on the plan. 5. Provide a water demand calculation on the plan. Mechanical 1. Model energy code calculations are not with the plan set. Provide Model energy code calculations based on the Civano energy code. 2. Show on the plan how the return air gets back to the unit.
11/29/2000 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
12/06/2000 DAVID RIVERA ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2001 ELAINE ROSE OUT TO CUSTOMER Completed