Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T00CM05374
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2000 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 11/21/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/24/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | |
| 11/24/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Provide the manufactures name and listing for the hood. Plumbing 1. Provide an expansion tank for the water heater on the cold water side. 2. Provide a union down stream of the manual shut off valve and before the fire system valve on the gas line going to the range. |
| 11/27/2000 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/06/2000 | RAY MORGAN | WWM | REVIEW | Approved | |
| 12/06/2000 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2001 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 12/20/2000 | CLAUDIA BUFORD | REJECT SHELF | Completed |
| 12/20/2000 | DELMA ROBEY | OUT TO CUSTOMER | Completed |