Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T00CM05255
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/09/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Show on the plan how the evapoative cooler complies with Sec 305.2 UMC1994 2. Provide access per Sec 321 Umc1994--show on the plan. |
11/15/2000 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/27/2000 | TGRIFFUS | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE COMPLETE ROOF PLANS OF BUILDING ON WHICH COOLING TOWER UPGRADES TAKE PLACE. 2. LOCATE WORK ON ROOF PLANS. 3. SHOW EXITING ON ROOF PLANS. 4. PROVIDE INSPECTION PROGRAM PER UAC SEC 302.5. 5. SUBMIT 2 SETS OF GRATING SHOP DRAWINGS AND CALCULATIONS. 6. SPECIAL INSPECTION REQUIRED FOR FIELD WELDING AND EPOXY ANCHORS. 7. CLARIFY HOW FIRE RATINGS AT PENETRATIONS THROUGH FIRE RATED ASSEMBLIES ARE MAINTAINED. |
11/27/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
11/30/2000 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/02/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
01/02/2001 | TAMI ACHONG | REJECT SHELF | Completed |
01/02/2001 | TAMI ACHONG | APPROVAL SHELF | Completed |