Permit Number: T00CM05255
Parcel: 12112404E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T00CM05255
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Show on the plan how the evapoative cooler complies with Sec 305.2 UMC1994 2. Provide access per Sec 321 Umc1994--show on the plan.
11/15/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
11/27/2000 TGRIFFUS BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE COMPLETE ROOF PLANS OF BUILDING ON WHICH COOLING TOWER UPGRADES TAKE PLACE. 2. LOCATE WORK ON ROOF PLANS. 3. SHOW EXITING ON ROOF PLANS. 4. PROVIDE INSPECTION PROGRAM PER UAC SEC 302.5. 5. SUBMIT 2 SETS OF GRATING SHOP DRAWINGS AND CALCULATIONS. 6. SPECIAL INSPECTION REQUIRED FOR FIELD WELDING AND EPOXY ANCHORS. 7. CLARIFY HOW FIRE RATINGS AT PENETRATIONS THROUGH FIRE RATED ASSEMBLIES ARE MAINTAINED.
11/27/2000 JIM EGAN FIRE REVIEW Approved
11/30/2000 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2001 TAMI ACHONG OUT TO CUSTOMER Completed
01/02/2001 TAMI ACHONG REJECT SHELF Completed
01/02/2001 TAMI ACHONG APPROVAL SHELF Completed