Permit Number - T00CM05152
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1) Provide GFCI in the bathroom 2) The panel schedule loads in panel D2 are not correctly placed. 3) Provide a roof top GFCI receptacle within 25' of the A/C. 4) The Alarm/Disconnect for the dental vaccuum lacks proper work clearance. 5) Clarify how you arrived at a 50% diversity for the receptacle loads in the load calculation for panel D2. 6) The receptacle serving the compressor cannot be a 20 amp duplex as depicted. 7) Provide the location of the A/C unit and unit disconnect. 8) Panel D2 is described as panel D in the panel schedule. 9) Panel D total load should reflect panel D2. 10) Provide total actual lighting load for D2 at 1.25 kVA. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/01/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |