Permit Number: T00CM05152
Parcel: 112043480

Review Status: Completed

Review Details: REVISION

Permit Number - T00CM05152
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved 1) Provide GFCI in the bathroom
2) The panel schedule loads in panel D2 are not correctly placed.
3) Provide a roof top GFCI receptacle within 25' of the A/C.
4) The Alarm/Disconnect for the dental vaccuum lacks proper work clearance.
5) Clarify how you arrived at a 50% diversity for the receptacle loads in the load calculation for panel D2.
6) The receptacle serving the compressor cannot be a 20 amp duplex as depicted.
7) Provide the location of the A/C unit and unit disconnect.
8) Panel D2 is described as panel D in the panel schedule.
9) Panel D total load should reflect panel D2.
10) Provide total actual lighting load for D2 at 1.25 kVA.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/01/2001 TAMI ACHONG OUT TO CUSTOMER Completed