Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T00CM04934
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
10/10/2000 | CBUFORD | WATER | REVIEW | Approved | |
10/16/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | |
10/16/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide the approved civil site plan with the Sewer & Water lines. 2. Condensate lines can not terminate on the roof as indicated in the keyed note #10. discharge in an approved location. Sec911.0 UPC1994 as amended Mechanical 1. Model energy code calculations are incorrect. Do not combine wall and Roof area in the OTTV calc's. Indicate on A-7 the R-Values for the insulation used. |
10/20/2000 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | GENERAL COMMENTS 1) Provide Model Energy Light budget calculations for both the interior and exterior of the building. See this site example below. Seal the calculation. 2) Please return the plans I have already reviewed if you decide to generate new plans. They are highlighted with yellow marker. E-3 1) Provide fixture cuts with catalog numbers for B and C. Please note the fixtures must comply with the Light Pollution Ordinance. 2) The TEP published fault current is 75,100 amps for a 1200 amp service. The downstream panels must be rated for 75,100 amps when protected by the fuses you have specified. In addition this series combination rating must be tested, listed, and labeled by an OSHA testing lab. See 99NEC 90-7, 110-3(a)(b), 110-9, 110-10, 110-22, 240-86(a)(b). 3) Panel HP4 contains 6 site lighting circuits. Provide a design or indicate they are for future use. MEC PRESCRIPTIVE ANALYSIS TABLE 6-5. OUTSIDE: ALLOWABLE, Building surface area: 372 ft/lin X 23 ft/av hgt X .25 w/ft^2 =2139 watts Canopy area light traffic 992 ft^2 X 4w/ft^2 = 3968 watts 6107 watts ACTUAL CONNECTED: Does not include PK lights. 2280 watts PASSES INSIDE: ALLOWABLE, 2160 ft^2 Occupied X 3.08 w/ft^2 = 6652 watts 5320 ft^2 Shell X 3.08 w/ft^2= 16385 watts 23037 watts Actual Occupied Space = 5377 watts Actual Shell Space= 64 watts 5441 watts PASSES |
11/02/2000 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE DOCUMENTS WITH MINIMUM OF 10 POINT FONT. (DWGS. AND SPEC.) 2.PROVIDE MORE READABLE COPY OF STRUCTURAL CALCULATIONS 3. CLARIFY ADDRESSING TO SHOW COMPLIANCE WITH COUNTY ADDRESSING ORDINANCE, SEE ATTACHMENT 4. CLARIFY INSULATION CONFORMS TO UBC SEC 707, FLAMESPREAD-RATING NOT TO EXCEED 25 AND A SMOKE DENSITY NOT TO EXCEED 450 5. INDICATE THE LOCATION AND DETAILS FOR DRAFTSTOPPING ON ROOF PLAN DRAWING A3, PER UBC SEC 708 6. CLARIFY WEATHER-RESISTIVE BARRIER ON DRAWINGS REF. A8 PER UBC SEC 1402 7. PROVIDE ICBO ER REPORT NUMBER FOR EIFS ON DRAWINGS PER UBC SEC 1403 8. PROVIDE INCREASED ROOF SLOPE (MINIMUM 3/8" IN 12 VS 1/4" IN 12 SHOWN ON DRAWING A3) OR PROVIDE ROOF SYSTEM CALCULATIONS PER AMENDED UBC SEC 1506.1 9. CLARIFY SAFETY GLAZING, PROVIDE SAFETY GLAZING ADJACENT TO STOREFRONT DOORS PER UBC SEC 2406.4 ITEM #6,WITHIN 24" OF JAMBS TO A HEIGHT OF 60" 10. SHOW FOAMPLASTIC INSULATON CONFORMS WITH UBC SEC 2602 11. PROVIDE SOILS REPORT WITH A MINIMUM OF ONE BORING TO A DEPTH OF 30 FEET PER ATTACHED MEMORANDUM RE: SIOLS REPORT DATED JULY 7, 1986 12 PROVIDE NAIL CALCULATIONS FOR: LATERAL DESIGN VALUES (Z) FOR NAILED CONNECTIONS SHALL BE MULTIPLIED BY ALL APPLICABLE ADJUSTMENT FACTORS ( SEE TABLE 23-III-A ) REF. STRUC CALCS PG L5, DWG 05/SD3 1994 UBC SEC 23, 2311, 2340, DIVISION III 13. EXPLAIN AND SHOW HOW CONTINUITY IS PROVIDED AT TOEDOWN 07/SD1 AND FOOTINGS AT SHEAR WALLS AND COLUMNS REF DWG #S1,01/SD1 AND 04/SD1 14. PROVIDE TRUSS SHOP DRAWINGS AS INDICATED ON STAMP 15. PROVIDE INSPECTION PROGRAM PER UAC SEC 302.5 16. FOLLOW STAMPS PROVIDED RE: SPECIAL INSPECTION SEE ATTACHMENTS |
11/04/2000 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | |
11/06/2000 | RAY MORGAN | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/29/2000 | TAMI ACHONG | APPROVAL SHELF | Completed |
11/08/2000 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
11/06/2000 | TAMI ACHONG | REJECT SHELF | Completed |