Permit Number: T00CM04705
Parcel: 126131380

Address:
4541 E TIMROD ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD

Permit Number - T00CM04705
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2000 DAVID RIVERA ZONING REVIEW Approved
10/18/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
10/18/2000 DRIVERA NPPO REVIEW Passed
10/30/2000 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T00CM04705
11/2/00

PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND.

GENERAL REQUIREMENTS

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINES ON THE PROPERTY AND WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM IF IT EXISTS.

FOUNDATION PLAN

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS, OR STATE THAT THE ASSUMED VALUE OF 1,000 PSF IS BEING USED.

2. A SOIL REPORT IS NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL CONDITIONS OF THE SUBDIVISION. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE CONSTRUCTION PLANS AND THE FOUNDATION DESIGN SHALL REFLECT SOIL REPORT RECOMMENDATIONS.

3. DIMENSION THE STEM WALL THICKNESS, FOOTING WIDTH THICKNESS AND DEPTH INTO UNDISTURBED SOIL FOR EACH FOOTING TYPE AND CONDITION.--------AS WELL AS MIN. 6" FROM NATURAL GRADE TO BOTTOM OF SILL PLATE

FLOOR PLAN

1. LABEL ALL ROOMS AND SPACES ADJACENT TO NEW ADDITION, SHOW ALL DOORS AND WINDOWS.

2. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS. --------FOR ROOMS ADJACENT TO ADDITION

3. SHOW COMPLIANCE WITH UBC SEC 1203.2 PROVIDING NATURAL LIGHT INTO ROOMS.
--------FOR ROOMS ADJACENT TO ADDITION

4. SHOW COMPLIANCE WITH UBC SEC 1203.3 PROVIDING NATURAL VENTILATION.
--------FOR ROOMS ADJACENT TO ADDITION

5. SHOW COMPLIANCE WITH UBC SEC 310.4 PROVIDING EGRESS FROM BEDROOMS OR BASEMENTS. SHOW MAXIMUM SILL HEIGHT OF 44".
--------FOR ROOMS ADJACENT TO ADDITION---IF APPLIES

6. NOTE THAT SHOWER ENCLOSURES SHALL BE FINISHED WITH MOISTURE RESISTANT GYPSUM BOARD AND CERAMIC TILE OR EQUAL TO A HEIGHT OF 70" ABOVE THE DRAIN. UBC SEC 807.1.3.

STRUCTURAL

1. SPECIFY MAKE AND MODEL NUMBER OF ALL CONNECTORS AND HANGERS.
POST BASE TYPE MISSING AT DETAIL 6-A2

ELEVATIONS

1. NOTE AND SPECIFY ALL ROOF SLOPES. MINIMUM ROOF SLOPE 3/8" PER FOOT. UBC SEC 1506.1 AND LOCAL AMENDMENT.

SECTIONS - DETAILS - MISCELLANEOUS NOTES

1. EAVES THAT EXTEND INTO THE REQUIRED 3' SETBACK FROM PROPERTY LINE MUST BE FIRE RATED-------PROVIDE 5/8" TYPE "X" GWB ON THE SOFFIT AREA OF THE EAVES.

PLUMBING PLAN

1. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWER HEADS 3 GALLONS PER MINUTE. UPC CH.15 W/LOCAL MODIFICATIONS.

2. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE
INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. PER. U.P.C. 410.7

ELECTRICAL

1. DESIGNATE THE LOCATION OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER OUTLETS AND SWITCHES.----------RECEPTS REQUIRED IN 6' PARTITION WALL-BOTH SIDES

2. BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS (NEC ART. 210-52(d)). G.F.C.I. PROTECTION REQUIRED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS: @ 791-5550 EXT. 112
11/03/2000 RAY MORGAN WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/13/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
11/06/2000 TAMI ACHONG APPROVAL SHELF Passed
11/03/2000 TAMI ACHONG REJECT SHELF Passed