Permit Number: T00CM04703
Parcel: 12316003A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T00CM04703
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2000 PETER MCLAUGHLIN ZONING REVIEW Approved
09/21/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
09/26/2000 JOE LINVILLE NPPO REVIEW Denied See attached comments.
10/16/2000 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T00CM004703
10/17/00

PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND.

GENERAL REQUIREMENTS

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLAN

1. ALL FOUNDATION HOLDDOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED, LOCATED AND DETAILED.

FLOOR PLAN

1. FIREPLACES:
-INDICATE FIREPLACE LOCATION, HEARTH SIZE AND MATERIALS

2. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING NOTE AVERAGE HEIGHT.-------NOTE: CHANGE IN ELEVATIONS REGARDING WALL HEIGHT WILL AFFECT CEILING HEIGHT AND/OR ROOF FRAMING--------CLARIFY

STRUCTURAL

1. BLOCKING REQUIRED UNDER BEARING WALL AT DETAIL 4-6

2. PROVIDE DETAILS FOR FRONT PORCH CONNECTIONS OF RIDGE TO JOISTS, JOISTS TO BEAM ,ETC.

3. SPECIFY MAKE AND MODEL NUMBER OF ALL CONNECTORS AND HANGERS.

SECTIONS - DETAILS - MISCELLANEOUS NOTES

1. PROVIDE A BUILDING CROSS SECTION. MORE THAN ONE MAY BE REQUIRED TO CLEARLY ILLUSTRATE HOW THE STRUCTURE IS BUILT.-----------PROVIDE FOR FRONT PORCH

PLUMBING PLAN

1. ISOMETRIC DRAWING OF WASTE LINES PROVIDED DOES NOT MATCH PLAN VIEW. LAV. MISSING, ROUTING AT LAVS. DIFFERENT,-------PLAN VIEW SHOWS TWO TRAPS ON ONE DIRTY ARM AT LAVS., NOT TO CODE

2. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. UPC CH.15 W/LOCAL MODIFICATIONS.

3. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATERHEATER (UPC SEC. 608.3)------MUST EXTEND TO OUTSIDE SOURCE NOT INTO WASTE LINES

4. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE
INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. PER. U.P.C. 410.7

MECHANICAL

1. GAS APPLIANCES SHALL COMPLY WITH UMC CH.7 COMBUSTION AIR REQUIREMENTS. DETAIL HOW THIS IS ACHIEVED.---------VENTS IN DOOR INTO HALL NOT ALLOWED FOR WATER HEATER AREA------EXTEND TO OUTSIDE, THE ATTIC, OR REMOVE DOOR

2. SHOW SIZES OF RETURN AIR DUCTS.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS: @ 791-5550 EXT. 112
10/19/2000 CBUFORD WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2000 TAMI ACHONG APPROVAL SHELF Completed
11/16/2000 TAMI ACHONG REJECT SHELF Completed
10/27/2000 TAMI ACHONG OUT TO CUSTOMER Completed