Permit Number: T00CM04582
Parcel: 116162870

Address:
845 N MAIN AV

Review Status: Completed

Review Details: SITE

Permit Number - T00CM04582
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2001 JIM JOHNSEN ENGINEERING REVIEW Approved
03/16/2001 JIM JOHNSEN SANITATION REVIEW Denied SUBJECT: Caridad Commissary
845 N. Main Avenue
T00CM04582


The site plan for the subject development, received on March 8, 2001, has been reviewed by the Engineering Section and is not acceptable for approval. The following comments are offered:

1. The limits of the 100-year floodplain and water surface elevations for the regulatory flow in Second Street, as identified in the drainage statement for this project should be shown on the site plan. Contrary to the statement in the response letter to previous review comments submitted by the consultant, this comment is still applicable. (Dev. Std. 2-02.2.1.A.15)
2. The site plan cannot be approved until the issue of acceptable maneuvering access for solid waste collection in accordance with Development Standard 6-01 is resolved. (Dev. Std. 2-02.2.1.A.32)
3. The consultant and developer should be aware that a grading plan is required for review and approval prior to issuance of a grading permit for this development. (Uniform Building Code Chapter 33, 1994 edition)

The above comments should be addressed on the site plan.

Jim Johnsen
Engineering Section
03/16/2001 JIM JOHNSEN FLOODPLAIN REVIEW Denied SUBJECT: Caridad Commissary
845 N. Main Avenue
T00CM04582


The site plan for the subject development, received on March 8, 2001, has been reviewed by the Engineering Section and is not acceptable for approval. The following comments are offered:

1. The limits of the 100-year floodplain and water surface elevations for the regulatory flow in Second Street, as identified in the drainage statement for this project should be shown on the site plan. Contrary to the statement in the response letter to previous review comments submitted by the consultant, this comment is still applicable. (Dev. Std. 2-02.2.1.A.15)
2. The site plan cannot be approved until the issue of acceptable maneuvering access for solid waste collection in accordance with Development Standard 6-01 is resolved. (Dev. Std. 2-02.2.1.A.32)
3. The consultant and developer should be aware that a grading plan is required for review and approval prior to issuance of a grading permit for this development. (Uniform Building Code Chapter 33, 1994 edition)

The above comments should be addressed on the site plan.

Jim Johnsen
Engineering Section
03/21/2001 PATRICIA GEHLEN ZONING REVIEW Denied
03/26/2001 JOE LINVILLE LANDSCAPE REVIEW Denied Native Plant Preservation Plan or approved application for exception required.
03/26/2001 PHIL SEADER HANDICAP-SITE REVIEW Denied
03/26/2001 JOE LINVILLE NPPO REVIEW Denied Submit Native Plant Preservation Plan or application for exception.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/18/2001 MVALDEZ OUT TO CUSTOMER Completed