Permit Number: T00CM04537
Parcel: 10409028D

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T00CM04537
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2000 JOHN HOGAN OPERATIONS REVIEW Approved
09/12/2000 GLENN MOYER PLANNING-CITY HALL REVIEW Approved
09/12/2000 CRAIG GROSS ZONING REVIEW Approved
09/12/2000 JIM EGAN FIRE REVIEW Approved
09/26/2000 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE DRAWING WITH MINIMUM 10 POINT FONT SIZE. 2. PROVIDE DETAILS AND MATERIAL SPECIFICATIONS FOR ANTENNA MOUNT REF. DWG C-1, C-3, INCLUDE CONNECTIONS AND WEATHERPROOFING AT ROOF. 3. PROVIDE LOAD ANALYSIS OF ROOF VS EQUIPMENT INSTALLED REF. DWG C-1.
09/29/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
ELECTRICAL REVIEW COMMENTS

DATE: September 29, 2000
ACTIVITY NUMBER: T00CM04537
PROJECT NAME: Cellular Antenna
PROJECT ADDRESS: 510 W. Limberlost
PROJECT REVIEWER: Randy Schuler, P.E.

E-1
1) Please clarify if the listing of the 100 amp panel will allow the installation of a 100 amp subfeed breaker. My experience has been that the largest size subfeed breaker allowed by the manufacturer is significantly smaller than the main. See 99NEC 110-3(b) requiring conformance with the listing and labeling of electrical equipment.
2) The conduit depths depicted on the plan are incorrect.
3) Plan sheets C-1 and C-2 indicate a 2.5" PVC conduit as the feeder to the power cabinet, page E-1 indicates a 1.25" RGS. In addition if PVC is utilized it must be schedule 80. I would also recommend that the PVC be painted with a latex paint to preclude the UV degradation of the conduit.
4) The services must be grouped together or provide justification for the 2nd service through 99NEC 230-2. Please note if the NEC will allow for the 2nd service provide placards and a common grounding electrode system. See 99NEC 230-2(e) and 250-58.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2000 TAMI ACHONG OUT TO CUSTOMER Completed
10/23/2000 TAMI ACHONG APPROVAL SHELF Completed
10/23/2000 TAMI ACHONG REJECT SHELF Completed