Permit Number: T00CM04532
Parcel: 13218171C

Address:
4855 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T00CM04532
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Floor sink can not be in or under walk-in bow.2. A manual shut off valve,union,& a fire system valve is required on the gas line prior to the cooking equipment, show on the isometric drawing.3. A 3" waste line can not be reduced to a 2" waste line. See yellow tab on plans.
10/20/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Detail 4 on M1.1r is incorrect. 2. Provide the manufactures name and listing for all of the equipment and fixtures to be used on the plan.
11/03/2000 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE PRIOR COMMENT #4
11/03/2000 RAY MORGAN WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2000 TAMI ACHONG OUT TO CUSTOMER Completed
12/08/2000 TAMI ACHONG APPROVAL SHELF Completed
11/03/2000 TAMI ACHONG REJECT SHELF Completed