Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T00CM04532
Parcel: 13218171C

Address:
4855 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T00CM04532
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2000 DAVID RIVERA ZONING REVIEW Approved
09/19/2000 JIM EGAN FIRE REVIEW Approved
09/21/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
09/22/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Total fixture units allowed on a 2" waste line is 8fu - floor sinks(2") are 3fu ea, FD 2" is 3fu ea, HS & MS's are 3fu ea, total amount on the line is 21fu. Floor sink inside of the walk-in is not allowed. 2. Venting of FS & FD does not comply with Sec 905.3UPC1994 3. Gas line is undersized for the load. Provide an isometric drawing of the gas line from the manual shut off valve, union,& fire system valve to the cooking equipment. 4. Provide a trap on the 3-comp sink. 5. Provide combustion/relief air for the WH per code on the plan.
09/22/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Detail 1 on M1.1 is incorrect and incomplete, the detail should inclued a detail on how the hood is supported from the structure. Note: Code requires a 3" air space above the hood that freely communicates to the one hoor chase. A one hoor ceiling is required above the hood and 18" beyond all sides of the hood. 2. Provide the manufactures name and listing for the hood and exaust fan. List all equipment to be used on the plan.
09/28/2000 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied 1.PROVIDE STUCCO DETAILS AND SPECIFICATIONS ON DRAWINGS 2. CLARIFY WHERE 20 % OF TOTAL COST OF ALTERATION IS SPENT ON ACCESSIBILE PATH OF TRAVEL PER UBC SEC. 1110 AND 1112 AS AMENDED, PROVIDE ITEMIZED ESTIMATE ON DRAWINGS. 3.PROVIDE MINIMUM STEEL REQUIRED BY UBC SEC. 2106.1.12.3 0.02 SQ. IN. IN CROSS-SECTIONAL AREA SHALL BE PROVIDED : 1) VERTICAL WALL REINFORCING AT EACH SIDE OF OPENING CONTINUOUSLY SUPPORT TO SUPPORT. 2) HORIZONTAL WALL REINFORCEMENTAT TOP OF WALL OPENINGS AND SHALL EXTEND NOT LESS THAN 24 INCHES PAST THE OPENING. REF: DETAIL B/A2.1. 4. PROVIDE HOOD SUPPORT CALCULATIONS AND DETAILS, ON DRAWINGS, INCLUDING FIRE TEST LISTING FOR FIRE-RESISTIVE ASSEMBLIES AND COMPLETE DETAILS FOR FIRE ASSEMBLIES (CEILING AT HOOD AND CHASE).
10/02/2000 RAY MORGAN WWM REVIEW Denied
10/02/2000 TGRIFFUS WATER REVIEW Approved
10/02/2000 TGRIFFUS FLOODPLAIN REVIEW Approved OK FOR FLOODPLAIN D. WILLIAMS

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2000 CLAUDIA BUFORD APPROVAL SHELF Passed
10/18/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
10/02/2000 DELMA ROBEY REJECT SHELF Passed