Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T00CM04532
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/11/2000 | DAVID RIVERA | ZONING | REVIEW | Approved | |
09/19/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
09/21/2000 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/22/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Total fixture units allowed on a 2" waste line is 8fu - floor sinks(2") are 3fu ea, FD 2" is 3fu ea, HS & MS's are 3fu ea, total amount on the line is 21fu. Floor sink inside of the walk-in is not allowed. 2. Venting of FS & FD does not comply with Sec 905.3UPC1994 3. Gas line is undersized for the load. Provide an isometric drawing of the gas line from the manual shut off valve, union,& fire system valve to the cooking equipment. 4. Provide a trap on the 3-comp sink. 5. Provide combustion/relief air for the WH per code on the plan. |
09/22/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Detail 1 on M1.1 is incorrect and incomplete, the detail should inclued a detail on how the hood is supported from the structure. Note: Code requires a 3" air space above the hood that freely communicates to the one hoor chase. A one hoor ceiling is required above the hood and 18" beyond all sides of the hood. 2. Provide the manufactures name and listing for the hood and exaust fan. List all equipment to be used on the plan. |
09/28/2000 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 1.PROVIDE STUCCO DETAILS AND SPECIFICATIONS ON DRAWINGS 2. CLARIFY WHERE 20 % OF TOTAL COST OF ALTERATION IS SPENT ON ACCESSIBILE PATH OF TRAVEL PER UBC SEC. 1110 AND 1112 AS AMENDED, PROVIDE ITEMIZED ESTIMATE ON DRAWINGS. 3.PROVIDE MINIMUM STEEL REQUIRED BY UBC SEC. 2106.1.12.3 0.02 SQ. IN. IN CROSS-SECTIONAL AREA SHALL BE PROVIDED : 1) VERTICAL WALL REINFORCING AT EACH SIDE OF OPENING CONTINUOUSLY SUPPORT TO SUPPORT. 2) HORIZONTAL WALL REINFORCEMENTAT TOP OF WALL OPENINGS AND SHALL EXTEND NOT LESS THAN 24 INCHES PAST THE OPENING. REF: DETAIL B/A2.1. 4. PROVIDE HOOD SUPPORT CALCULATIONS AND DETAILS, ON DRAWINGS, INCLUDING FIRE TEST LISTING FOR FIRE-RESISTIVE ASSEMBLIES AND COMPLETE DETAILS FOR FIRE ASSEMBLIES (CEILING AT HOOD AND CHASE). |
10/02/2000 | RAY MORGAN | WWM | REVIEW | Denied | |
10/02/2000 | TGRIFFUS | WATER | REVIEW | Approved | |
10/02/2000 | TGRIFFUS | FLOODPLAIN | REVIEW | Approved | OK FOR FLOODPLAIN D. WILLIAMS |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/18/2000 | CLAUDIA BUFORD | APPROVAL SHELF | Passed |
10/18/2000 | CLAUDIA BUFORD | OUT TO CUSTOMER | Passed |
10/02/2000 | DELMA ROBEY | REJECT SHELF | Passed |