Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD
Permit Number - T00CM04421
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2000 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 09/06/2000 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 09/20/2000 | TERRY STEVENS | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T00CM04421 9/20/00 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND. GENERAL REQUIREMENTS 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. 3. ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF THE STATE BOARD OF TECHNICAL REGISTRATION. SITE PLAN 1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINES ON THE PROPERTY AND WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM IF IT EXISTS. FOUNDATION PLAN 1. DIMENSION THE STEM WALL THICKNESS, FOOTING WIDTH THICKNESS AND DEPTH INTO UNDISTURBED SOIL FOR EACH FOOTING TYPE AND CONDITION. ON DETAILS FLOOR PLAN 1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS AS WELL AS THE LOCATIONS OF TEMPERED GLASS (UBC SEC 2406.4). REQUIRED WITHIN 24" OF A DOOR AND AT TUB IN MASTER BATH 2. SHOW COMPLIANCE WITH UBC SEC 1203.2 PROVIDING NATURAL LIGHT INTO ROOMS. MASTER BEDROOM DOES NOT MEET MIN. 10%OF FLOOR AREA 3. SHOW COMPLIANCE WITH UBC SEC 1203.3 PROVIDING NATURAL VENTILATION. DINING ROOM HAS NO VENTILATION---MIN. 5% OF FLOOR AREA 4. SHOW COMPLIANCE WITH UBC SEC 310.4 PROVIDING EGRESS FROM BEDROOMS OR BASEMENTS. SHOW MAXIMUM SILL HEIGHT OF 44". MASTER BEDROOM WINDOWS DO NOT MEET MIN. 5.7 SQ. FT. OPENABLE AREA 5. NOTE THAT SHOWER ENCLOSURES SHALL BE FINISHED WITH MOISTURE RESISTANT GYPSUM BOARD AND CERAMIC TILE OR EQUAL TO A HEIGHT OF 70" ABOVE THE DRAIN. UBC SEC 807.1.3. 6.DETAIL AND SPECIFY STAIR WIDTH, RISE AND RUN, LANDING WIDTH, HANDRAIL HEIGHTS, GUARDRAIL HEIGHT AND INTERMEDIATE RAIL SPACING. PER UBC SEC 1006 AND SEC 509. STRUCTURAL 1. PROVIDE DESIGN FOR LINTELS IN EXCESS OF PRESCRIPTIVE METHOD AND CALLOUT LINTEL SIZES FOR EACH OPENING--- NOT WITH SCHEDULE PROVIDED. BUILDER HAS NO IDEA AS TO POUNDS PER LINEAR FOOT 2. PROVIDE A HEADER SCHEDULE OR NOTE HEADER SIZES AT ALL BEARING OPENINGS ON FRAMING OR FLOOR PLANS. MISSING AT FLOOR FRAMING OVER STAIRS 3. SPECIFY MAKE AND MODEL NUMBER OF ALL CONNECTORS AND HANGERS. 4. PROVIDE STAIRWAY CONNECTION DETAILS AND STRINGER SIZES. PRE FABRICATED METAL STAIR SHALL HAVE MANUFACTURER'S SPECIFICATIONS ATTACHED TO THE PLANS. 5. PROVIDE DESIGN FOR PATIO WALL IN EXCESS OF 6' IN HEIGHT ELEVATIONS 1. NOTE AND SPECIFY ALL ROOF SLOPES. MINIMUM ROOF SLOPE 3/8" PER FOOT. UBC SEC 1506.1 AND LOCAL AMENDMENT. CLARIFY ROOF SLOPE ---2 DIFFERENT SLOPES INDICATED 2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH UBC SEC 1505.3. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY. SECTIONS - DETAILS - MISCELLANEOUS NOTES 1. NOTE AND SPECIFY THE SIZE, SPACING AND LENGTH OF EMBEDMENT OF ANCHOR BOLTS FOR SILL PLATES, TOP PLATES AND LEDGERS. 2. DETAIL AND NOTE ALL MASONRY WALL REINFORCEMENT. UBC CH.21 ICBO REPORT ER-4203 TABLE ONE CALLS FOR MIN. WALL REINFORCEMENT OF #3 REBAR IN EACH CELL-----PLANS INDICATE #4 IN EVERYOTHER CELL CHANGE OR PROVIDE DESIGN 3. MASONRY WALLS SHALL BE ANCHORED TO FLOORS AND ROOFS WHICH PROVIDE LATERAL SUPPORT FOR THE WALL. DETAIL A POSITIVE DIRECT CONNECTION CAPABLE OF RESISTING THE HORIZONTAL FORCES. SEE UBC SEC 2109. PLUMBING PLAN 1. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES.SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED CLEANOUTS.--------REQUIRED FOR TWO STORY STRUCTRES 2. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATERHEATER (UPC SEC. 608.3) MECHANICAL 1. SHOW SIZES OF RETURN AIR DUCTS. ELECTRICAL 1. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12 INCHES AND SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 INCHES FROM A RECEPTACLE OUTLET. (N.E.C. ART. 210-52(c)(1).) G.F.C.I. PROTECTION REQUIRED. 2. PROVIDE ELECTRICAL LOAD CALCULATIONS FOR EXISTING STRUCTURE ALSO. MISCELLANEOUS 1. PROVIDE MODEL ENERGY CALCULATIONS BASE ON RASTA WALLS WITH R-11 NOT R-36. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: TERRY STEVENS: @ 791-5550 EXT. 112 |
| 09/21/2000 | JOE LINVILLE | NPPO | REVIEW | Passed | n/a |
| 09/22/2000 | RAY MORGAN | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/30/2000 | TAMI ACHONG | APPROVAL SHELF | Completed |
| 11/30/2000 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 11/30/2000 | TAMI ACHONG | REJECT SHELF | Completed |