Permit Number: T00CM04320
Parcel: 11520198A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T00CM04320
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2000 CRAIG GROSS ZONING REVIEW Approved
09/13/2000 GLENN MOYER PLANNING-CITY HALL REVIEW Approved
09/25/2000 JIM EGAN FIRE REVIEW Approved
09/26/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
ELECTRICAL REVIEW COMMENTS

DATE: September 26, 2000
ACTIVITY NUMBER: T00CM004320
PROJECT NAME: Cell Site
PROJECT ADDRESS: 1400 N. Silverbell Rd.
PROJECT REVIEWER: Randy Schuler, P.E.
A2, A3, E2
1) The electrical service and generator receptacle lack proper work clearance. See 99NEC 110-26
10/04/2000 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1) PROVIDE COVERED CABLE TRAY DETAILS - MATERIALS OF CONSTRUCTION, CONNECTIONS TO MONOPOLE,ETC.,ON DRAWINGS. S2) CLARIFY DESIGN CRITERIA THIS SITE IS IN TUCSON, PIMA COUNTY VS MARICOPA COUNTY NOTED IN COVER LETTER DATED MAY 16, 2000 TO VOICESTREAM FROM PAUL J. FORD AND COMPANY; WAS APPLICABLE CRITERIA USED IN DESIGN? S3) PROVIDE PROPER SEAL AND SIGNATURE ON CALCULATIONS. S4) PROVIDE COMPLETE DETAILS OF ANTENNAS ON DRAWINGS. S5) PROVIDE COMPLETE DETAILS OF ANTENNA SUPPORTS ON DRAWINGS , INCLUDING MATERIAL SPECIFICATIONS AND CONNECTIONS.
10/11/2000 TGRIFFUS OPERATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2000 CLAUDIA BUFORD APPROVAL SHELF Passed
11/08/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
11/08/2000 CLAUDIA BUFORD REJECT SHELF Passed