Permit Number: T00CM04181
Parcel: Unknown

Address:
5051 E GLENN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T00CM04181
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Indicate on the plan that buildings #1,#3,#7&#9 will require a Back Water Valve.
12/11/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) It appears the electrical equipment rack is located within the retention/detention area. When the run off accumulates within the basin how will it be possible for an electrician to access the service.
2) Provide a description of the area light. Include a fixture catalog cut and number along with the submittal.
3) The equipment bonding jumper between the meter and panel A must be a # 4 cu. Minimum. 99NEC 250-102(c).
4) The compressor pumps appear to be single phase however they are described as 3 phase. In addition if they are single phase the load for each compressor is approximately 1.6 kVA. 99NEC 430-6(a)(1) and 430-22(a).
12/12/2000 RAY MORGAN WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2000 TAMI ACHONG OUT TO CUSTOMER Completed
12/15/2000 CLAUDIA BUFORD REJECT SHELF Completed