Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T00CM04181
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Indicate on the plan that buildings #1,#3,#7	 will require a Back Water Valve. |
| 12/11/2000 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) It appears the electrical equipment rack is located within the retention/detention area. When the run off accumulates within the basin how will it be possible for an electrician to access the service. 2) Provide a description of the area light. Include a fixture catalog cut and number along with the submittal. 3) The equipment bonding jumper between the meter and panel A must be a # 4 cu. Minimum. 99NEC 250-102(c). 4) The compressor pumps appear to be single phase however they are described as 3 phase. In addition if they are single phase the load for each compressor is approximately 1.6 kVA. 99NEC 430-6(a)(1) and 430-22(a). |
| 12/12/2000 | RAY MORGAN | WWM | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/15/2000 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 12/15/2000 | CLAUDIA BUFORD | REJECT SHELF | Completed |