Permit Number: T00CM04065
Parcel: 13705501Q

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T00CM04065
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2000 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
12/26/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Incorrect Model Energy Code Calculations submitted. Provide ASHRAE/IES Standard 90.1-1999 Program.
12/26/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. A 2" condensate line can not go into a 1 1/2" Lav tail piece. Take the condensate line to the mop sink with an air gap. 2. The T&P shall discharge per Sec 608.5UPC1994.
12/27/2000 JIM EGAN FIRE REVIEW Approved
12/27/2000 SREEVES WWM REVIEW Denied
12/28/2000 CBUFORD ELECTRICAL-COMMERCIAL REVIEW Approved
12/28/2000 DAVID RIVERA ZONING REVIEW Approved
12/28/2000 CBUFORD WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2001 TAMI ACHONG REJECT SHELF Completed
01/16/2001 TAMI ACHONG OUT TO CUSTOMER Completed