Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/19/2000 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
12/26/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Incorrect Model Energy Code Calculations submitted. Provide ASHRAE/IES Standard 90.1-1999 Program. |
12/26/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. A 2" condensate line can not go into a 1 1/2" Lav tail piece. Take the condensate line to the mop sink with an air gap. 2. The T&P shall discharge per Sec 608.5UPC1994. |
12/27/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
12/27/2000 | SREEVES | WWM | REVIEW | Denied | |
12/28/2000 | CBUFORD | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/28/2000 | DAVID RIVERA | ZONING | REVIEW | Approved | |
12/28/2000 | CBUFORD | WATER | REVIEW | Approved |