Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T00CM04064
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/02/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1.Fix red lines on the black line prints. 2. A 2" condensate line can not go to a LAV tailpiece, take it to the mop sink with an air gap. 3. Provide an expansion tank for the water heater on the C.W. side down stream of the M.S.O.V. Per Sec608.3 par3 UPC1994. |
01/02/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Incorrect model energy code calc's. Talked to engineer 1,2,01. |
01/03/2001 | DAVID RIVERA | ZONING | REVIEW | Approved | |
01/03/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
12/19/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
12/19/2000 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
12/20/2000 | TOM CLARK | WATER | REVIEW | Approv-Cond | |
12/26/2000 | DROBEY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/27/2000 | RAY MORGAN | WWM | REVIEW | Denied |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/05/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
01/03/2001 | TAMI ACHONG | REJECT SHELF | Completed |