Permit Number: T00CM04064
Parcel: 13705501Q

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T00CM04064
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1.Fix red lines on the black line prints. 2. A 2" condensate line can not go to a LAV tailpiece, take it to the mop sink with an air gap. 3. Provide an expansion tank for the water heater on the C.W. side down stream of the M.S.O.V. Per Sec608.3 par3 UPC1994.
01/02/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Incorrect model energy code calc's. Talked to engineer 1,2,01.
01/03/2001 DAVID RIVERA ZONING REVIEW Approved
01/03/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
12/19/2000 JIM EGAN FIRE REVIEW Approved
12/19/2000 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
12/20/2000 TOM CLARK WATER REVIEW Approv-Cond
12/26/2000 DROBEY ELECTRICAL-COMMERCIAL REVIEW Approved
12/27/2000 RAY MORGAN WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
01/05/2001 TAMI ACHONG OUT TO CUSTOMER Completed
01/03/2001 TAMI ACHONG REJECT SHELF Completed