Permit Number: T00CM02963
Parcel: 132042740

Address:
3191 E 44TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T00CM02963
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2000 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
09/15/2000 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/18/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model energy code calculations shall apply to the warehouse if evaporative cooling is used. Redo calc"s. 2. Provide a complete Mechanical design. 3. Comply with SEC 1202.2.1 UBC1994 in the office.
09/18/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide a civil site plan showing an approved sewer & water going to the new building. Provide the slope of the sewer line. Building sewer does not comply with Sec 719.0UPC1994. 2. Water line is undersized for the fixture units & distance. Water fixture units are incorrect.