Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T00CM02963
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2000 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 09/15/2000 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/18/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Model energy code calculations shall apply to the warehouse if evaporative cooling is used. Redo calc"s. 2. Provide a complete Mechanical design. 3. Comply with SEC 1202.2.1 UBC1994 in the office. |
| 09/18/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide a civil site plan showing an approved sewer & water going to the new building. Provide the slope of the sewer line. Building sewer does not comply with Sec 719.0UPC1994. 2. Water line is undersized for the fixture units & distance. Water fixture units are incorrect. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2000 | TAMI ACHONG | APPROVAL SHELF | Completed |
| 10/13/2000 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 10/13/2000 | TAMI ACHONG | REJECT SHELF | Completed |