10/20/2000 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T00CM02887
6/27/00------2ND REVIEW 10/20/00

PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER, NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND.

GENERAL REQUIREMENTS

1. ALL CORRECTIONS AND REVISIONS SHALL BE LEGIBLE AND SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. RED LINING OF FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN

1. SEWER LINE AS INDICATED IS GOING INTO ADJOINING PROPERTY, IF SEWER IS BEING ATTACHED TO NEIGHBORS SEWER LINE A SEWER USE AGREEMENT IS REQUIRED
SEWER USE AGREEMENT MUST BE SIGNED BY BOTH PROPERTY OWNERS AND RECORDED WITH THE COUNTY RECORDERS OFFICE

STRUCTURAL

1. PROVIDE COMPLETE ROOF AND FLOOR FRAMING PLANS. SHOW SIZE, SPACING AND SPAN OF ALL FRAMING MEMBERS, TRUSSES, JOISTS, RAFTERS, BEAMS, GLU-LAMS, LINTELS HEADERS, LEDGERS AND BLOCKING.
HEADER SIZES MISSING FOR ALL OPENINGS IN INTERIOR BEARING WALLS--LINTEL SCHEDULE INADEQUATE----USE 2- 31/2X31/2X1/4 FOR OPENINGS LESS THAN 4'------USE 4X31/2X5/16 FOR OPENINGS 4' TO 7'

ELEVATIONS

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH U.B.C. SEC 1505.3. NOTE LOCATION AND SIZE OF ALL VENTS NEEDED TO COMPLY.----------VENT CALCS. SUPPLIED DO NOT MEET CODE ALSO SQ. FT. OF STRUCTURE IS WRONG

ELECTRICAL

1. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS AND DISCONNECTS.

2. ELECTRICAL LOAD CALC'S. DO NOT MEET CODE---------SQ. FT. OF STRUCTURE IS NOT 2240---------HEAT PUMPS ARE CALC'D. AT 125%

MISC.

1. PROVIDED MODEL ENERGY CALCULATIONS ARE DONE INCORRECT.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: TERRY STEVENS @ 791-5550 EXT. 112