Permit Number: T00CM02782
Parcel: 11702144A

Address:
1015 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T00CM02782
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2000 ANY FIRE REVIEW Approved
07/03/2000 ANY MECHANICAL-COMMERCIAL REVIEW Approved
07/03/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Review, Randy Schuler, P.E. July 3, 2000
T00CM02782
Page E2
1) The electrical sitre plan calls out new 200 amp service entrance drop. The electrical floor plan calls out a 400 amp drop.
2) 99NEC 230-2 allows one service per building.
3) Keynote 7 is used twice on the electrical floor plan.
4) The service disconnects must be grouped together. See 99NEC 230-40ex2, 230-72.
5) The 200 amp disconnect interior to the building (in front of the existing service) impedes the work clearance of the existing service. The disconnect appars to be mounted in an area designated "storage area". Clearly defin what the storage area is (e.g.) building, chain link, raised slab, ect.
E3
1) The ground between the new 400 amp term can and the service disconnect must be increased to a minimum of 1/0 cu.
99NEC 250-102(c)
2) There are more disconnects on the one line than on the floor plan on page E2.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2000 CLAUDIA BUFORD APPROVAL SHELF Passed
08/08/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
08/08/2000 CLAUDIA BUFORD REJECT SHELF Passed