Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T00CM02777
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/24/2001 | TGRIFFUS | HANDICAP-SITE | REVIEW | Denied | |
01/24/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SEE PRIOR COMMENT #7. EXIT VESTIBULE INCLUDING CORRIDOR #3 TO BE ONE-HOUR FIRE-RATED. SHOW HOW FIRE-RATING IS PROVIDED AT WALLS, ROOF/CEILING ASSEMBLIES, PENETRATIONS( INCLUDING DOORS). 2. SEE PRIOR COMMENT #16. 1. FIRE-RATING OF DOORS #6, #7, #8, #( AT VESTIBULE (SEE ABOVE). 2. SHOW ON DRAWINGS HOW HARDWARE CONFORMS TO UBC SEC #1004 AND SEC#1106.10, FOR OPENABILITY AND ACCESSIBILITY. 3. SEE PRIOR COMMENT #17. 1. SPECIFY FULLY HANDRAILS ie: STRUCTURAL DESIGN REQUIREMENTS. 2. SHOW AT EACH SIDE OF STAIR. 3. SHOW REQUIRED EXTENSIONS ON HANDRAILS. 4. PROVIDE TWO SETS OF HANDRAILS SHOP DRAWINGS AND CALCULATIONS, (AS NOTED). 5. SPECIFY LIMITS ON STAIR : RISE 7" AND RUN 11" PER UBC SEC 1006, ON DRAWINGS. 4. SEE PRIOR COMMENT #18. 1. 60" x 60" LANDING REQUIRED AT DOOR #2-CLARIFY. 2. RE-ARRANGE VESTBULE. 3. PROVIDE TWO SETS OF RAMP HANDRAIL SHOP DRAWINGS AND CALCULATIONS. 4. SPECIFY FULLY RAMP HANDRAILS ie: STRUCTURAL DESIGN LOADS. 5. SHOW REQUIRED EXTENSIONS ON RAMP HANDRAILS. 5. SEE PRIOR COMMENT #20. 1. CLARIFY 60" DIAMETER UNOBSTRUCTED TURN-AROUND , SHOW ON PLAN. 2. FULLY LOCATE AND DIMENSION FIXTURES IN TOILET ROOM : 1. UNDER LAVATORY SECTION CONFORMING TO UBC SEC 1106.11.7. 2. GRAB BARS, DIMENSION , LOCATION. 3. HEIGHT OF WATER CLOSET SEAT ABOVE FLOOR. 4. BABY CHANGING STATION. 3. SHOW CLEAR FLOOR AREA ON PLAN FOR FIXTURES. 6. SEE PRIOR COMMENT #21. CLARIFY ACCESSIBILITY OF WATER FOUNTAIN. 7. SEE PRIOR COMMENT #23. WHAT IS ICBO ER # ? PRIOR COMMENTS ATTACHED. |
02/02/2001 | TGRIFFUS | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
02/02/2001 | TGRIFFUS | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
12/15/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
12/18/2000 | DOUG WILLIAMS | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/02/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |